H2-xx: MFDO Setting Values
Setting Value
Function
Description
Ref.
0
During Run
The terminal activates when the Run command is input and when the drive is outputting voltage.
ON : Drive is running
OFF : Drive is stopping
1
Zero Speed
The terminal activates when the output frequency <
E1-09 [Minimum Output Frequency]
or
b2-01 [DC Injection/Zero
SpeedThreshold]
.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the reference.
A1-02 Setting
Control method selection
Parameter Used as the Reference
0
V/f
E1-09
1
CL-V/f
E1-09
2
OLV
b2-01
3
CLV
E1-09
4
AOLV
E1-09
5
OLV/PM
E1-09
6
AOLV/PM
E1-09
7
CLV/PM
b2-01
8
EZOLV
E1-09
ON : Output frequency < value of
E1-09
or
b2-01
.
OFF : Output frequency ≥ value of
E1-09
or
b2-01
.
2
Speed Agree 1
The terminal turns on when the output frequency is in the range of the frequency reference ±
L4-02 [Speed Agree
Detection Width]
.
Note:
•
The detection function operates in the two motor rotation directions.
•
The drive outputs the motor speed status when
A1-02 = 3, 7 [CLV, CLV/PM]
. It also outputs the motor speed
status when
A1-02 = 4
and
n4-72 = 1
.
ON : The output frequency is in the range of
“
frequency reference ±
L4-02
”
.
OFF : The output frequency does not align with the frequency reference although the drive is running.
3
User-Set Speed Agree 1
The terminal activates when the output frequency is in the range of
L4-01 [Speed Agree Detection Level]
±
L4-02
[Speed Agree Detection Width]
and in the range of the frequency reference ±
L4-02
.
Note:
•
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the
forward/reverse detection level.
•
The drive outputs the motor speed status when
A1-02 = 3, 7 [CLV, CLV/PM]
. It also outputs the motor speed
status when
A1-02 = 4
and
n4-72 = 1
.
ON : The output frequency is in the range of
“
L4-01
±
L4-02
”
and the range of frequency reference ±
L4-02
.
OFF : The output frequency is not in the range of
“
L4-01
±
L4-02
”
or the range of frequency reference ±
L4-02
.
4
Frequency Detection 1
The terminal deactivates when the output frequency >
L4-01 [Speed Agree Detection Level] + L4-02 [Speed Agree
Detection Width]
. After the terminal turns off, the terminal continues to remain off until the output frequency reaches
the level set with
L4-01
.
Note:
•
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the
forward/reverse detection level.
•
The drive outputs the motor speed status when
A1-02 = 3, 7 [CLV, CLV/PM]
. It also outputs the motor speed
status when
A1-02 = 4
and
n4-72 = 1
.
ON : The output frequency is less than the value of
L4-01
or does not exceed the value of
L4-01
+
L4-02
.
OFF : The output frequency >
L4-01
+
L4-02
.
5
Frequency Detection 2
The terminal activates when the output frequency is higher than the value of
L4-01 [Speed Agree Detection Level]
.
After the terminal activates, the terminal stays activated until the output frequency =
L4-01
-
L4-02
.
Note:
•
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the
forward/reverse detection level.
•
The drive outputs the motor speed status when
A1-02 = 3, 7 [CLV, CLV/PM]
. It also outputs the motor speed
status when
A1-02 = 4
and
n4-72 = 1
.
ON : The output frequency is higher than the value of
L4-01
.
OFF : The output frequency <
“
L4-01
-
L4-02
”
, or ≤
L4-01
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 172: ...1 22 Parameters Changed by PM Motor Code Selection 172 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...