YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
393
Note:
shows the result of the configuration when
L4-07 = 1 [Speed Agree Detection Selection = Detection Always Enabled]
. The
default setting of
L4-07
is
0 [No detection during baseblock]
. When the speed agreement detection selection is
“
No Detection during
Baseblock
”
, the terminal is deactivated when the drive output stops.
■
5: Frequency Detection 2
Setting Value
Function
Description
5
Frequency Detection 2
The terminal activates when the output frequency is higher than the value of
L4-01 [Speed Agree Detection Level]
. After the
terminal activates, the terminal stays activated until the output frequency =
L4-01
-
L4-02
.
Note:
•
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the forward/reverse detection level.
•
The drive outputs the motor speed status when
A1-02 = 3, 7 [CLV, CLV/PM]
. It also outputs the motor speed status when
A1-02 = 4
and
n4-
72 = 1
.
ON : The output frequency is higher than the value of
L4-01
.
OFF : The output frequency < “
L4-01
-
L4-02
”, or
≤
L4-01
.
Figure 2.94 Frequency Detection 2 Time Chart
■
6: Drive ready
Setting Value
Function
Description
6
Drive ready
The terminal activates when the drive is ready and running.
The terminal deactivates in these conditions:
•
When the power supply is OFF
•
During a fault
•
When there is problem with the control power supply
•
When there is a parameter configuration error and the drive cannot operate although there is a Run command
•
When you enter a Run command and it immediately triggers an overvoltage or undervoltage fault because the drive
has an overvoltage or undervoltage fault during stop
•
When the drive is in Programming Mode and will not accept a Run command
■
7: DC Bus Undervoltage
Setting Value
Function
Description
7
DC Bus Undervoltage
The terminal activates when the DC bus voltage or control circuit power supply is less than the voltage set with
L2-05
[Undervoltage Detection Lvl (Uv1)]
. The terminal also turns on when there is a fault with the DC bus voltage.
ON : The DC bus voltage is less than the setting value of
L2-05
.
OFF : The DC bus voltage is more than the setting value of
L2-05
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV