YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
51
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F1-51
(03D3)
PG-F3 PGoH Detection
Level
The drive will detect
PGoH [Encoder (PG) Hardware Fault]
if the value of this parameter
is smaller than the value of
.
Note:
This function is enabled when
F1-20 = 1 [Encoder 1 PCB Disconnect Detect =
Enabled]
.
80%
(1 - 100%)
F1-52
(03D4)
Serial Encoder Comm
Speed
Sets the communication speed between the PG-F3 option and the serial encoder.
0 : 1M/9600bps
1 : 500k/19200bps
2 : 1M/38400bps
0
(0 - 2)
◆
F2: Analog Input Option
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F2-01
(038F)
Analog Input Function
Selection
Sets the input method for the analog reference used with AI-A3.
0 : 3 Independent Channels
1 : 3 Channels Added Together
0
(0, 1)
F2-02
(0368)
RUN
Analog Input Option Card
Gain
Sets the analog reference gain as a percentage when the maximum output frequency is
100%.
Note:
•
Set
F2-01 = 1 [Analog Input Function Selection = 3 Channels Added Together]
to
enable this function.
•
Parameter
A1-02 [Control Method Selection]
selects which parameter is the
maximum output frequency.
–
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
–
A1-02 = 8
:
E9-02 [Maximum Speed]
100.0%
(-999.9 - +999.9%)
F2-03
(0369)
RUN
Analog Input Option Card
Bias
Sets the analog reference bias as a percentage when the maximum output frequency is
100%.
Note:
•
Set
F2-01 = 1 [Analog Input Function Selection = 3 Channels Added Together]
to
enable this function.
•
Parameter
A1-02 [Control Method Selection]
selects which parameter is the
maximum output frequency.
–
A1-02 ≠ 8 [EZOLV]
:
E1-04 [Maximum Output Frequency]
–
A1-02 = 8
:
E9-02 [Maximum Speed]
0.0%
(-999.9 - +999.9%)
◆
F3: Digital Input Option
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F3-01
(0390)
Digital Input Function
Selection
Sets the data format of digital input signals. This parameter is enabled when
o1-03 = 0 or 1
[Frequency Display Unit Selection = 0.01 Hz or 0.01% (100% = E1-04)]
.
Note:
When
o1-03 = 2
or
3 [Revolutions Per Minute (RPM) or User Units (o1-10 & o1-11)]
,
the input signal will be BCD. The
o1-03
value sets the setting units.
0 : BCD, 1% units
1 : BCD, 0.1% units
2 : BCD, 0.01% units
3 : BCD, 1 Hz units
4 : BCD, 0.1 Hz units
5 : BCD, 0.01 Hz units
6 : BCD (5-digit), 0.02 Hz
7 : Binary input
8 : Multi-Function Digital Input
8
(0 - 8)
F3-03
(03B9)
Digital Input Data Length
Select
Sets the number of bits to set the frequency reference with
DI-A3
.
0 : 8-bit
1 : 12-bit
2 : 16-bit
2
(0 - 2)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV