Table 22: Protections settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.15
Underload Fault
(broken belt/dry
pump)
0
3
0
713
See P3.9.2.
P3.9.16
Underload Protec-
tion: Field Weaken-
ing Area Load
10.0
150.0
%
50.0
714
P3.9.17
Underload Protec-
tion: Zero Frequency
Load
5.0
150.0
%
10.0
715
P3.9.18
Underload Protec-
tion: Time Limit
2.00
600.00
s
20.00
716
P3.9.19
Response to Field-
bus Communication
Fault
0
4
3
733
See P3.9.1
P3.9.20
Slot Communication
Fault
0
3
2
734
See P3.9.2.
P3.9.21
Thermistor Fault
0
3
0
732
See P3.9.2.
P3.9.22
Response to PID1
Supervision Fault
0
3
2
749
See P3.9.2.
P3.9.23
Response to PID2
Supervision Fault
0
3
2
757
See P3.9.2.
P3.9.25
TempFault Signal
0
6
0
739
0 = Not Used
1 = Temp. Input 1
2 = Temp. Input 2
3 = Temp. Input 3
4 = Temp. Inputs 1-2
5 = Temp. Inputs 2-3
6 = Temp. Inputs 1-3
P3.9.26
TempAlarm Limit
-30.0
200
130.0
741
P3.9.27
TempFault Limit
-30.0
200
155.0
742
P3.9.28
TempFault Response
0
3
2
740
0 = No response
1 = Alarm
2 = Fault (Stop accord-
ing to stop mode)
3 = Fault (Stop by
coasting)
P3.9.29 *
Response to Safe
Torque Off (STO)
Fault
0
2
2
775
0 = No action
1 = Alarm
2 = Fault (Stop by
coasting)
PARAMETERS MENU