Table 34: Feedback settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.12.3.1
Feedback Function
1
9
1
333
1 = Only Source1 in use
2 = SQRT(Source1);
(Flow=Constant x
SQRT(Pressure))
3 = SQRT(Source1-
Source 2)
4 = SQRT(Source 1) +
SQRT (Source 2)
5 = Source 1 + Source 2
6 = Source 1 - Source 2
7 = MIN (Source 1,
Source 2)
8 = MAX (Source 1,
Source 2)
9 = MEAN (Source 1,
Source 2)
P3.12.3.2
Feedback Function
Gain
-1000.0
1000.0
%
100.0
1058
P3.12.3.3
Feedback 1 Source
Selection
0
14
2
334
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = AI5
6 = AI6
7 = ProcessDataIn1
8 = ProcessDataIn2
9 = ProcessDataIn3
10 = ProcessDataIn4
11 = ProcessDataIn5
12 = ProcessDataIn6
13 = ProcessDataIn7
14 = ProcessDataIn8
P3.12.3.4 Feedback 1 Minimum -200.00
200.00
%
0.00
336
P3.12.3.5
Feedback 1 Maxi-
mum
-200.00
200.00
%
100.00
337
P3.12.3.6
Feedback 2 Source
Selection
0
14
0
335
See P3.12.3.3.
P3.12.3.7 Feedback 2 Minimum -200.00
200.00
%
0.00
338
See P3.12.3.4.
M3.12.3.8
Feedback 2 Maxi-
mum
-200.00
200.00
%
100.00
339
See P3.12.3.5.
PARAMETERS MENU
VACON · 81
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]