5.12
GROUP 3.12: PID-CONTROLLER 1
Table 32: PID controller 1 basic settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.12.1.1
PID Gain
0.00
1000.00
%
100.00
118
P3.12.1.2
PID Integration Time
0.00
600.00
s
1.00
119
P3.12.1.3
PID Derivation Time
0.00
100.00
s
0.00
132
P3.12.1.4
Process Unit Selec-
tion
1
40
1
1036
P3.12.1.5
Process Unit Min
Varies
Varies
Varies
0
1033
P3.12.1.6
Process Unit Max
Varies
Varies
Varies
100
1034
P3.12.1.7
Process Unit Deci-
mals
0
4
2
1035
P3.12.1.8
Error Inversion
0
1
0
340
0 = Normal (Feedback
< Setpoint -> Increase
PID output)
1 = Inverted (Feedback
< Setpoint -> Decrease
PID output )
P3.12.1.9
Dead Band hystere-
sis
Varies
Varies
Varies
0
1056
P3.12.1.10
Dead Band Delay
0.00
320.00
s
0.00
1057
VACON · 78