5.3
GROUP 3.3: CONTROL REFERENCE SETTINGS
Table 12: Control reference settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.3.1
Minimum Frequency
0.00
P3.3.2
Hz
0.00
101
P3.3.2
Maximum Frequency
P3.3.1
320.00
Hz
0.00
102
P3.3.3
I/O Control Refer-
ence A Selection
1
11
6
117
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 reference
8 = Motor potentiome-
ter
9 = Average (AI1, AI2)
10 = Min (AI1, AI2)
11 = Max (AI1, AI2)
P3.3.4
I/O Control Refer-
ence B Selection
1
11
4
131
P3.3.5
Keypad Ctrl Refer-
ence Selection
1
8
2
121
1 = Preset Frequency 0
2 = Keypad
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 reference
8 = Motor potentiome-
ter
P3.3.6
Keypad Reference
P3.3.1
P3.3.2
Hz
0.00
184
P3.3.7
Keypad Direction
0
1
0
123
0 = Forward
1 = Reverse
P3.3.8
Keypad reference
copy
0
2
1
181
0 = Copy reference
1 = Copy ref & Run
state
2 = No copying
P3.3.9
Fieldbus Control
Reference Selection
1
8
3
122
1 = Preset frequency 0
2 = Keypad
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 reference
8 = Motor potentiome-
ter
P3.3.10
Preset Frequency
Mode
0
1
0
182
0 = Binary coded
1 = Number of inputs
VACON · 58
PARAMETERS MENU
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205