Table 46: The total counter parameters in the diagnostics menu
Index
Parameter
Min
Max
Unit
Default
ID
Description
V4.4.14
Power On Time (text
keypad)
hh:min:
ss
The power on time in
hours, minutes and
seconds.
V4.4.15
Start Command
Counter
2295
The number of times
that the power unit has
been started.
6.5
TRIP COUNTERS
Table 47: The trip counter parameters in the diagnostics menu
Index
Parameter
Min
Max
Unit
Default
ID
Description
P4.5.1
Energy Trip Counter
Varies
2296
You can reset this
counter. In the text dis-
play: the highest
energy unit that the
display shows is MW. If
the counted energy
becomes more than
999.9 MW, no unit
shows on the display.
Resetting the
counter
•
In the text display:
Push the OK but-
ton for 4 s.
•
In the graphical
display: Push OK.
A Reset counter
page shows. Push
OK again.
P4.5.3
Operating Time
(graphical keypad)
a d
hh:min
2299
You can reset this
counter. See instruc-
tions in P4.5.1 above.
P4.5.4
Operating Time (text
keypad)
a
The operating time in
total years.
P4.5.5
Operating Time (text
keypad)
d
The operating time in
total days.
P4.5.6
Operating Time (text
keypad)
hh:min:
ss
The operating time in
hours, minutes and
seconds.
DIAGNOSTICS MENU
VACON · 91
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
6