Table 17: Standard I/O board analogue output settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.5.4.1.1
AO1 function
0
PID
feed-
back
2
10050
0 = TEST 0% (Not used)
1 = TEST 100%
2 = Output freq (0 -
fmax)
3 = Freq reference (0 -
fmax)
4 = Motor speed (0 -
Motor nominal speed)
5 = Output current (0 -
I
n
Motor)
6 = Motor torque (0 -
T
n
Motor)
7 = Motor power (0 -
P
n
Motor)
8 = Motor voltage (0 -
U
n
Motor)
9 = DC link voltage (0 -
1000V)
10 = PID1 output
(0-100%)
11 = PID2 output
(0-100%)
12 = ProcessDataIn1
(0-100%)
13 = ProcessDataIn2
(0-100%)
14 = ProcessDataIn3
(0-100%)
15 = ProcessDataIn4
(0-100%)
16 = ProcessDataIn5
(0-100%)
17 = ProcessDataIn6
(0-100%)
18 = ProcessDataIn7
(0-100%)
19 = ProcessDataIn8
(0-100%)
P3.5.4.1.1
AO1 function
0
PID
feed-
back
2
10050
P3.5.4.1.2
AO1 filter time
0.0
300.0
s
1.0
10051 0 = No filtering
P3.5.4.1.3 AO1 minimum signal
0
1
0
10052 0 = 0 mA / 0V
1 = 4 mA / 2V
P3.5.4.1.4 AO1 minimum scale
Varies
Varies
Varies
0.0
10053
VACON · 68
PARAMETERS MENU
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205