0%
100%
50%
C
B
A
D
E
0 mA
20 mA
10 mA
[Hz]
[%]
10 Hz
40 Hz
0 Hz
Fig. 25: The scaling of the AO1 signal
A. Analogue output signal
B. AO min scale
C. AO max scale
D. Max freq reference
E. Output frequency
10.6
FIELDBUS DATA MAP
P3.6.1 FB DATAOUT 1 SELECTION (ID 852)
Use this parameter to select the data that is sent to the fieldbus with the ID number of the
parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel.
For example, value 25.5 on the display equals 255.
P3.6.2 FB DATAOUT 2 SELECTION (ID 853)
Use this parameter to select the data that is sent to the fieldbus with the ID number of the
parameter or monitor value.
The data is scaled to an unsigned 16-bit format according to the format on the control panel.
For example, value 25.5 on the display equals 255.
VACON · 148
PARAMETER DESCRIPTIONS