Selection
number
Selection name
Description
0
Test 0% (Not used)
The analogue output is set to 0% or 20% so that it agrees
with parameter P3.5.4.1.3.
1
TEST 100%
The analogue output is set to 100% of the signal (10V /
20mA).
2
Output frequency
The actual output frequency from 0 to Maximum frequency
reference.
3
Frequency reference
The actual frequency reference from 0 to Maximum fre-
quency reference.
4
Motor speed
The actual motor speed from 0 to Motor nominal speed.
5
Output current
The output current of the drive from 0 to Motor nominal cur-
rent.
6
Motor torque
The actual motor torque from 0 to motor nominal torque
(100%).
7
Motor power
The actual motor power from 0 to Motor nominal power
(100%).
8
Motor voltage
The actual motor voltage from 0 to Motor nominal voltage.
9
DC-link voltage
The actual DC-link voltage 0…1000V.
10
PID1 output
The output of the PID controller 1 (0…100%).
11
PID2 output
The PID controller 2 output (0…100%).
12
Process Data In 1
Process Data In 1: 0…10000 (this agrees with 0…100.00%).
13
Process Data In 2
Process Data In 2: 0…10000 (this agrees with 0…100.00%).
14
Process Data In 3
Process Data In 3: 0…10000 (this agrees with 0…100.00%).
15
Process Data In 4
Process Data In 4: 0…10000 (this agrees with 0…100.00%).
16
Process Data In 5
Process Data In 5: 0…10000 (this agrees with 0…100.00%).
17
Process Data In 6
Process Data In 6: 0…10000 (this agrees with 0…100.00%).
18
Process Data In 7
Process Data In 7: 0…10000 (this agrees with 0…100.00%).
19
Process Data In 8
Process Data In 8: 0…10000 (this agrees with 0…100.00%).
NOTE!
For ProcessDataIn, use value without a decimal separator, for example, 5000
=50.00%.
P3.5.4.1.2 AO1 FILTER TIME (ID 10051)
Use this parameter to set the filtering time for the analog signal.
VACON · 146
PARAMETER DESCRIPTIONS
10