2
In the Edit mode, the slot value DigIN SlotA is
underlined and blinks. If you have more digital
inputs available in your I/O, for example, because of
option boards in slots C, D or E, make a selection of
them.
STOP
READY
I/O
Ext Fault Close
P3.5.1.7
ID:405
Min:
Max:
DigIN SlotA.3
3
To activate the terminal 3, push the arrow button
Right again.
STOP
READY
I/O
Ext Fault Close
P3.5.1.7
ID:405
Min:
Max:
DigIN SlotA.3
4
To change the terminal to 6, push the arrow button
Up 3 times. Accept the change with the OK button.
STOP
READY
I/O
Ext Fault Close
P3.5.1.7
ID:405
Min:
Max:
DigIN SlotA.6
5
If the digital input DI6 was already used for some
other function, a message shows on the display.
Change one of these selections.
STOP
READY
I/O
ID:
At least one digital input has
been selected to several
operations.
To prevent possible unwanted
operations, please check all
digital input selection parameters.
PARAMETER DESCRIPTIONS
VACON · 135
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
10
Содержание 100 HVAC
Страница 1: ...vacon 100 hvac ac drives application manual ...
Страница 2: ......
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 200: ......