Table 16: Digital output settings on standard I/O board
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.5.3.2.1
Basic RO1 Function
0
41
2
11001
29 = Motor 3 control
30 = Motor 4 control
31 = Motor 5 control
32 = Reserved
33 = Reserved
34 = Maintenance
alarm
35 = Maintenance fault
36 = Thermistor fault
37 = Motor switch
38 = PreHeat
39 = kWh pulse output
40 = Run Indication
41 = Selected Param.
Set
P3.5.3.2.2
Basic R01 ON Delay
0.00
320.00
s
0.00
11002
P3.5.3.2.3
Basic R01 OFF Delay
0.00
320.00
s
0.00
11003
P3.5.3.2.4
Basic R02 Function
0
41
3
11004 See P3.5.3.2.1.
P3.5.3.2.5
Basic R02 ON Delay
0.00
320.00
s
0.00
11005 See P3.5.3.2.2.
P3.5.3.2.6
Basic R02 OFF Delay
0.00
320.00
s
0.00
11006 See P3.5.3.2.3.
P3.5.3.2.7
Basic R03 Function
0
41
1
11007 See P3.5.3.2.1.
P3.5.3.2.8
P3.5.3.2.9
THE DIGITAL OUTPUTS OF THE EXPANDER SLOTS C, D AND E
Shows only the parameters for the outputs on option boards in slots C, D and E. Make the
selections as in Basic RO1 Function (P3.5.3.2.1).
This group or these parameters are not visible if there are no digital outputs in slots C, D or
E.