5.8
GROUP 3.8: LIMIT SUPERVISIONS
Table 21: Limits supervision settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.8.1
Supervision #1 Item
Selection
0
7
0
1431
0 = Output frequency
1 = Frequency reference
2 = Motor current
3 = Motor torque
4 = Motor power
5 = DC-link voltage
6 = Analogue input 1
7 = Analogue input 2
P3.8.2
Supervision #1 Mode
0
2
0
1432
0 = Not used
1 = Low limit supervision
(output active over limit)
2 = High limit supervision
(output active under
limit)
P3.8.3
Supervision #1 Limit
Varies
Varies
Varies
25.00
1433
P3.8.4
Supervision #1 Limit
Hysteresis
Varies
Varies
Varies
5.00
1434
P3.8.5
Supervision #2 Item
Selection
0
7
1
1435 See P3.8.1
P3.8.6
Supervision #2 Mode
0
2
0
1436 See P3.8.2
P3.8.7
Supervision #2 Limit
Varies
Varies
Varies
40.00
1437 See P3.8.3
P3.8.8
Supervision #2 Limit
Hysteresis
Varies
Varies
Varies
5.00
1438 See P3.8.4
PARAMETERS MENU
VACON · 71