5.5
GROUP 3.5: I/O CONFIGURATION
Table 14: Digital input settings
Index
Parameter
Default
ID
Description
P3.5.1.1
Control Signal 1 A
DigIN SlotA.1
403
P3.5.1.2
Control Signal 2 A
DigIN SlotA.2
404
P3.5.1.3
Control Signal 1 B
DigIN Slot0.1
423
P3.5.1.4
Control Signal 2 B
DigIN Slot0.1
424
P3.5.1.5
I/O B Control Force
DigIN Slot0.1
425
P3.5.1.6
I/O B Reference Force
DigIN Slot0.1
343
P3.5.1.7
External Fault Close
DigIN SlotA.3
405
OPEN = OK
CLOSED = External fault
P3.5.1.8
External Fault Open
DigIN Slot0.2
406
OPEN = External fault
CLOSED = OK
P3.5.1.9
Fault Reset Close
DigIN SlotA.6
414
P3.5.1.10 Fault Reset Open
DigIN Slot0.1
213
P3.5.1.11 Run Enable
DigIN Slot0.2
407
P3.5.1.12 Run Interlock 1
DigIN Slot0.2
1041
P3.5.1.13 Run Interlock 2
DigIN Slot0.2
1042
P3.5.1.14 Motor Preheat ON
DigIN Slot0.1
1044
OPEN = No action.
CLOSED = Uses the DC current of the
motor preheat in Stop state. Used
when the value of P3.1.2.5 is 2.
P3.5.1.15 Preset Frequency Selection 0 DigIN SlotA.4
419
P3.5.1.16 Preset Frequency Selection 1 DigIN SlotA.5
420
P3.5.1.17 Preset Frequency Selection 2 DigIN Slot0.1
421
P3.5.1.18 Timer 1
DigIN Slot0.1
447
P3.5.1.19 Timer 2
DigIN Slot0.1
448
P3.5.1.20 Timer 3
DigIN Slot0.1
449
P3.5.1.21 Disable Timer Function
DigIN Slot0.1
1499
CLOSED = Disables the Timer func-
tions and resets timers.
OPEN = Enables the Timer functions.
P3.5.1.22 PID1 Setpoint Boost
DigIN Slot0.1
1046
OPEN = No boost
CLOSED = Boost
PARAMETERS MENU
VACON · 61
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]