Input type (graphi-
cal display)
Input type
(text dis-
play)
Slot
Input #
Explanation
DigIN
dI
A
1
Digital input #1 (terminal 8) on a board in Slot A
(standard I/O board).
DigIN
dI
A
2
Digital input #2 (terminal 9) on a board in Slot A
(standard I/O board).
DigIN
dI
A
3
Digital input #3 (terminal 10) on a board in Slot
A (standard I/O board).
DigIN
dI
A
4
Digital input #4 (terminal 14) on a board in Slot
A (standard I/O board).
DigIN
dI
A
5
Digital input #5 (terminal 15) on a board in Slot
A (standard I/O board).
DigIN
dI
A
6
Digital input #6 (terminal 16) on a board in Slot
A (standard I/O board).
The function External Fault Close, the location of which is the menu M3.5.1, is parameter
P3.5.1.11. It gets the default value DigIN SlotA.3 in the graphical display, and dI A.3 in the text
display. After this selection, a digital signal to the digital input DI3 (terminal 10) controls
External Fault Close.
Index
Parameter
Default
ID
Description
P3.5.1.11
External fault
close
DigIN SlotA.3
405
OPEN = OK
CLOSED = External fault
To change the input from DI3 to, for example, DI6 (terminal 16) on the standard I/O, obey
these instructions.
PROGRAMMING IN THE GRAPHICAL DISPLAY
1
Make a selection of a parameter. To go into the Edit
mode, push the arrow button Right.
STOP
READY
I/O
Digital inputs
Ext Fault Open
Fault Reset Close
DigINSlotA3
DigINSlot0.2
DigINSlotA6
Ext Fault Close
P3.5.1.7
ID:405
VACON · 134
PARAMETER DESCRIPTIONS