Table 15: Analogue input settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.5.2.1
AI1 Signal Selection
AnIN
SlotA.1
377
P3.5.2.2
AI1 Filter Time
0.0
300.0
s
1.0
378
P3.5.2.3
AI1 Signal Range
0
1
0
379
0 = 0–10V / 0–20mA
1 = 2–10V / 4–20mA
P3.5.2.4
AI1 Custom. Min
-160.00
160.00
%
0.00
380
P3.5.2.5
AI1 Custom. Max
-160.00
160.00
%
100.00
381
P3.5.2.6
AI1 Signal Inversion
0
1
0
387
0 = Normal
1 = Signal inverted
P3.5.2.7
AI2 Signal Selection
AnIN
SlotA.2
388
See P3.5.2.1
P3.5.2.8
AI2 Filter Time
0.0
300.0
s
1.0
389
See P3.5.2.2
P3.5.2.9
AI2 Signal Range
0
1
1
390
See P3.5.2.3
P3.5.2.10
AI2 Custom. Min
-160.00
160.00
%
0.00
391
See P3.5.2.4
P3.5.2.11
AI2 Custom. Max
-160.00
160.00
%
100.00
392
See P3.5.2.5
P3.5.2.12
AI2 Signal Inversion
0
1
0
398
See P3.5.2.6
P3.5.2.13
AI3 Signal Selection
AnIN
Slot0.1
141
See P3.5.2.1
P3.5.2.14
AI3 Filter Time
0.0
300.0
s
1.0
142
See P3.5.2.2
P3.5.2.15
AI3 Signal Range
0
1
0
143
See P3.5.2.3
P3.5.2.16
AI3 Custom. Min
-160.00
160.00
%
0.00
144
See P3.5.2.4
P3.5.2.17
AI3 Custom. Max
-160.00
160.00
%
100.00
145
See P3.5.2.5
P3.5.2.18
AI3 Signal Inversion
0
1
0
151
See P3.5.2.6
P3.5.2.19
AI4 Signal Selection
AnIN
Slot0.1
152
See P3.5.2.1
P3.5.2.20
AI4 Filter Time
0.0
300.0
s
1.0
153
See P3.5.2.2
P3.5.2.21
AI4 Signal Range
0
1
0
154
See P3.5.2.3
P3.5.2.22
AI4 Custom. Min
-160.00
160.00
%
0.00
155
See P3.5.2.4
P3.5.2.23
AI4 Custom. Max
-160.00
160.00
%
100.00
156
See P3.5.2.5
P3.5.2.24
AI4 Signal Inversion
0
1
0
162
See P3.5.2.6
VACON · 64