*) This parameter is not visible if the drive does not have support for safety torque off
functionality.
5.10
GROUP 3.10: AUTOMATIC RESET
Table 23: Autoreset settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.10.1
Automatic Reset
0
1
1
731
0 = Disabled
1 = Enabled
P3.10.2
Restart Function
0
1
1
719
0 = Flying start
1 = According to P3.2.4.
P3.10.3
Wait Time
0.10
10000.00
s
0.50
717
P3.10.4
Trial Time
0.00
10000.00
s
60.00
718
P3.10.5
Number of Trials
1
10
4
759
P3.10.6
Autoreset: Under-
voltage
0
1
1
720
0 = No
1 = Yes
P3.10.7
Autoreset: Over-
voltage
0
1
1
721
0 = No
1 = Yes
P3.10.8
Autoreset: Over-
current
0
1
1
722
0 = No
1 = Yes
P3.10.9
Autoreset: AI Low
0
1
1
723
0 = No
1 = Yes
P3.10.10
Autoreset: Unit
Overtemperature
0
1
1
724
0 = No
1 = Yes
P3.10.11
Autoreset: Motor
Overtemperature
0
1
1
725
0 = No
1 = Yes
P3.10.12
Autoreset: Exter-
nal Fault
0
1
0
726
0 = No
1 = Yes
P3.10.13
Autoreset: Under-
load Fault
0
1
0
738
0 = No
1 = Yes
P3.10.14
PID Supervision
0
1
0
15538 0 = No
1 = Yes