AFA4000/2
Airflow Monitor / p.113
8.1.1.4
BACNet settings menu
Menu item
Instructions
Device Instance
Use the
↑
/
↓
buttons to set the value for a digit, then press
Mute
to go to the next digit.
Station ID
Set the Station ID.
Baudrate
Set the Baudrate:
•
1200
•
2400
•
4800
•
9600
•
14400
•
19200
•
38400
•
57600
Parity
Set the parity:
•
None
•
Odd
•
Even
Max Masters
Set the maximum number of AFA4000 devices on the
network.
Done
Return to the
Monitor config menu
(section 8.1.1).