AFA4000/2
Airflow Monitor / p.54
5.5
Start up
5.5.1
AFA4000/2
The AFA4000/2 must be field-calibrated once the room air supply and exhaust is
proportionally balanced.
When the unit is powered up, the following sequence of events occurs:
The alarm performs a self-test of its functions and audible alarm which takes
approximately 3 seconds. At the end of the delay, the unit will do one of two things:
When the Airflow monitor has been calibrated, the unit enters normal operating mode.
The monitor displays airflow velocity, LEDs and the audible alarm is enabled.
If the Airflow monitor has not been calibrated, the unit displays the message
Requires set
up, press Mute to continue
.
Follow the instructions in the
Calibration
section (section 7.1).
5.5.2
AFA4000/2/AS
The AFA4000/2/AS must be field-calibrated once the room air supply and exhaust is
proportionally balanced.
When the unit is powered up, the following sequence of events occurs:
1.
The alarm performs a self-test of its functions and audible alarm which takes
approximately 3 seconds.
2.
At the end of the delay, the unit will do one of five things:
•
When the Airflow monitor has been calibrated, the unit enters normal operating
mode. The monitor displays airflow velocity, LEDs and the audible alarm is enabled.
•
When the Airflow monitor has not been calibrated, the unit displays the message
Requires set up, press
Mute
to continue.
•
When the Auto Sash Controller has been calibrated, the unit enters normal
operating mode. The Controller displays status and alarms in the status window.
•
When the Auto Sash Controller is connected and has not been calibrated, the
status window displays the message Auto Sash Not Configured.
Содержание AFA4000/2
Страница 1: ...AFA4000 2 Airflow monitor Installation and operating manual Issue 1 ...
Страница 50: ...AFA4000 2 Airflow Monitor p 50 Figure 21 AFA4000 2 typical connection diagram ...
Страница 51: ...AFA4000 2 Airflow Monitor p 51 Figure 22 AFA4000 2 AS typical connection diagram ...
Страница 52: ...AFA4000 2 Airflow Monitor p 52 5 4 Dimensions Figure 23 AFA4000 2 and AFA4000 2 AS dimensions ...
Страница 53: ...AFA4000 2 Airflow Monitor p 53 Figure 24 SM7 airflow sensor dimensions ...
Страница 64: ...AFA4000 2 Airflow Monitor p 64 Figure 34 Side views of a rack and pinion drive typical installation ...
Страница 87: ...AFA4000 2 Airflow Monitor p 87 Figure 61 Adjusting the personnel sensor beam angle away from the fume hood ...
Страница 90: ...AFA4000 2 Airflow Monitor p 90 6 10 Auto Sash System Control Box general wiring diagram ...
Страница 127: ...AFA4000 2 Airflow Monitor p 127 ...
Страница 140: ...AFA4000 2 Airflow Monitor p 140 Figure 69 Typical connection diagram ...
Страница 144: ...AFA4000 2 Airflow Monitor p 144 Figure 70 Connection diagram with RS232 485 converter ...