AFA4000/2
Airflow Monitor / p.32
4.2
Auto Sash control options
To open / close the fume hood sash the Auto Sash Controller is fitted with:
•
A Tiptronic open/close control via the Sash Position Sensor.
•
A Sash Low micro-switch
•
A Sash Low proximity switch
4.2.1
Auto Sash Controller with Tiptronic open / close control
Tiptronic Open / Close control is the default control setup. It functions via a Sash
Position Sensor (sprung potentiometer) with a draw wire (1.2m long) attached to either
the sash or the counterweight. The Auto Sash Controller can then be calibrated to give
three methods of operation:
Method A - Close only
•
The bottom position is calibrated.
•
The sash automatically drives to the bottom position,
when the user is not present.
•
Press the
↓
pushbutton to drive the sash to the
bottom position, when the user is present.
•
The
↑
pushbutton is disabled.
Method B - 2 Positions
•
The bottom and mid-positions are calibrated.
•
The sash automatically drives to the bottom position,
when the user is not present.
•
Press the
↓
pushbutton to drive the sash to the
bottom position, when the user is present.
•
Press the
↑
pushbutton to drive the sash to the mid-
position, when the user is present.
•
When the Tiptronic feature is enabled, manually tip
the sash upwards and the sash will drive to the mid-
position.
•
Manually tip the sash downwards and the sash will
drive to the bottom position.
Содержание AFA4000/2
Страница 1: ...AFA4000 2 Airflow monitor Installation and operating manual Issue 1 ...
Страница 50: ...AFA4000 2 Airflow Monitor p 50 Figure 21 AFA4000 2 typical connection diagram ...
Страница 51: ...AFA4000 2 Airflow Monitor p 51 Figure 22 AFA4000 2 AS typical connection diagram ...
Страница 52: ...AFA4000 2 Airflow Monitor p 52 5 4 Dimensions Figure 23 AFA4000 2 and AFA4000 2 AS dimensions ...
Страница 53: ...AFA4000 2 Airflow Monitor p 53 Figure 24 SM7 airflow sensor dimensions ...
Страница 64: ...AFA4000 2 Airflow Monitor p 64 Figure 34 Side views of a rack and pinion drive typical installation ...
Страница 87: ...AFA4000 2 Airflow Monitor p 87 Figure 61 Adjusting the personnel sensor beam angle away from the fume hood ...
Страница 90: ...AFA4000 2 Airflow Monitor p 90 6 10 Auto Sash System Control Box general wiring diagram ...
Страница 127: ...AFA4000 2 Airflow Monitor p 127 ...
Страница 140: ...AFA4000 2 Airflow Monitor p 140 Figure 69 Typical connection diagram ...
Страница 144: ...AFA4000 2 Airflow Monitor p 144 Figure 70 Connection diagram with RS232 485 converter ...