6.
Installation: Auto Sash Controller
As the size and format of individual fume hoods vary, the installation instructions that
follow are general. The principles outlined should remain valid in all cases.
Note: Before starting installation, ensure that the sash is free to move in its runners. Use
silicon spray on the sash runners or adjust the sash runner's alignment when the
sash does not move freely.
6.1
Auto Sash Control Unit
6.1.1
Mounting the unit
The Auto Sash Control Unit can be mounted as follows:
•
Screwed flat to the outside of the fume hood roof - horizontal mounting
Note: For horizontal mounting, the control box should always be mounted with the lid /
front panel facing upwards.
•
Screwed to the outside wall of fume hood wall - vertical mounting
Figure 25: Auto Sash Control Unit Lid/Front
Panel
Figure 26: Rear of Auto Sash Control Unit
Содержание AFA4000/2
Страница 1: ...AFA4000 2 Airflow monitor Installation and operating manual Issue 1 ...
Страница 50: ...AFA4000 2 Airflow Monitor p 50 Figure 21 AFA4000 2 typical connection diagram ...
Страница 51: ...AFA4000 2 Airflow Monitor p 51 Figure 22 AFA4000 2 AS typical connection diagram ...
Страница 52: ...AFA4000 2 Airflow Monitor p 52 5 4 Dimensions Figure 23 AFA4000 2 and AFA4000 2 AS dimensions ...
Страница 53: ...AFA4000 2 Airflow Monitor p 53 Figure 24 SM7 airflow sensor dimensions ...
Страница 64: ...AFA4000 2 Airflow Monitor p 64 Figure 34 Side views of a rack and pinion drive typical installation ...
Страница 87: ...AFA4000 2 Airflow Monitor p 87 Figure 61 Adjusting the personnel sensor beam angle away from the fume hood ...
Страница 90: ...AFA4000 2 Airflow Monitor p 90 6 10 Auto Sash System Control Box general wiring diagram ...
Страница 127: ...AFA4000 2 Airflow Monitor p 127 ...
Страница 140: ...AFA4000 2 Airflow Monitor p 140 Figure 69 Typical connection diagram ...
Страница 144: ...AFA4000 2 Airflow Monitor p 144 Figure 70 Connection diagram with RS232 485 converter ...