AFA4000/2
Airflow Monitor / p.95
‘
Display Smoothing
’
parameter in the
cal config
menu. The monitor will display the
velocity value as a rolling average over time and is adjustable over 1 to 100 seconds.
•
Do not use fully open and fully closed sash positions for the calibration points. The
recommended positions are normal operating height (for example,
500 mm 20”) for
the first sample and approximately half the sash opening (for example, 250
mm 10”)
for the second sample. Do not close the sash below 150mm.
7.2
Auto Sash Controller 1, 2 or 3 position.
This section describes the calibration of the Auto Sash Controller from the
AFA4000/2/AS.
Note: Refer to section 7.4 to calibrate the Auto Sash Controller from the Auto Sash keypad
1.
From the
Run Screen
press and hold the
Mute
button for 5 seconds until the
Main
Menu
is displayed.
2.
Use the
↑
/
↓
buttons to select
Set Up Auto Sash
. The display shows the message
TEL
SASH CLOSER
.
3.
Press the
Mute
button to display the current Hardware and Software version, for
example,
1. HW2.0 FW1.1
.
4.
Press the
↓
button to scroll down and select
Setup Menu
and press
Mute
.
5.
Enter the password (the factory default password is 1-0-0-1) and press
Mute
to
continue.
6.
In the Setup menu the controller displays
System Profile
.
7.
Use the
↓
button to scroll through the menu, select
Sash 1 Settings
and press
Mute
.
8.
In the
S1 Settings menu
, the display will show
1. Enabled
.
9.
Use the ↓ button to scroll through the menu and select
8. Calibration
and press
Mute
.
10.
Follow the on-screen instructions and set the sash to the centre opening, for example,
250 mm.
11.
Press the
↓
button to find which arrow represents the sash closing and press
Mute
.
This step shows the controller which direction the motor needs to drive to close the
sash.
12.
Close the sash and press
Mute
. This step sets the sash position sensor output, 0 V
position.
Содержание AFA4000/2
Страница 1: ...AFA4000 2 Airflow monitor Installation and operating manual Issue 1 ...
Страница 50: ...AFA4000 2 Airflow Monitor p 50 Figure 21 AFA4000 2 typical connection diagram ...
Страница 51: ...AFA4000 2 Airflow Monitor p 51 Figure 22 AFA4000 2 AS typical connection diagram ...
Страница 52: ...AFA4000 2 Airflow Monitor p 52 5 4 Dimensions Figure 23 AFA4000 2 and AFA4000 2 AS dimensions ...
Страница 53: ...AFA4000 2 Airflow Monitor p 53 Figure 24 SM7 airflow sensor dimensions ...
Страница 64: ...AFA4000 2 Airflow Monitor p 64 Figure 34 Side views of a rack and pinion drive typical installation ...
Страница 87: ...AFA4000 2 Airflow Monitor p 87 Figure 61 Adjusting the personnel sensor beam angle away from the fume hood ...
Страница 90: ...AFA4000 2 Airflow Monitor p 90 6 10 Auto Sash System Control Box general wiring diagram ...
Страница 127: ...AFA4000 2 Airflow Monitor p 127 ...
Страница 140: ...AFA4000 2 Airflow Monitor p 140 Figure 69 Typical connection diagram ...
Страница 144: ...AFA4000 2 Airflow Monitor p 144 Figure 70 Connection diagram with RS232 485 converter ...