AFA4000/2
Airflow Monitor / p.136
9.
Use the
↑
/
↓
buttons to select
Show Temperature
, use the
↑
/
↓
buttons to select
Enabled
or
Not Enabled
10.
Use the
↑
/
↓
buttons to select
Offset
, use the
↑
/
↓
buttons to set the offset, then
select
Done
.
11.
In the
Monitor Config Menu
use the
↑
/
↓
buttons to select
Low Temperature
Relay
, use the
↑
/
↓
buttons to set the relay output.
12.
In the
Monitor Config Menu
use the
↑
/
↓
buttons to select
High Temperature
Relay
, use the
↑
/
↓
buttons to set the relay output, select
Done > Run
.
9.1.1
Testing
Once the temperature sensor function has been configured the temperature will display
in the diagnostics menu I/O Status.
The sensor data screen is described in section 13.2.
9.2
Optional input function
–
close sash alarm
A Close Sash alarm informs the user that the fume cupboard sash has been left open.
The alarm can be set with a time delay before activation, this allow the user to briefly
leave the fume cupboard sash open. The alarm can be set to repeat if the sash is left
open for prolonged periods.
The alarm function uses a PIR occupancy sensor and is connected in series with a micro-
switch input to detect the sash position.
Содержание AFA4000/2
Страница 1: ...AFA4000 2 Airflow monitor Installation and operating manual Issue 1 ...
Страница 50: ...AFA4000 2 Airflow Monitor p 50 Figure 21 AFA4000 2 typical connection diagram ...
Страница 51: ...AFA4000 2 Airflow Monitor p 51 Figure 22 AFA4000 2 AS typical connection diagram ...
Страница 52: ...AFA4000 2 Airflow Monitor p 52 5 4 Dimensions Figure 23 AFA4000 2 and AFA4000 2 AS dimensions ...
Страница 53: ...AFA4000 2 Airflow Monitor p 53 Figure 24 SM7 airflow sensor dimensions ...
Страница 64: ...AFA4000 2 Airflow Monitor p 64 Figure 34 Side views of a rack and pinion drive typical installation ...
Страница 87: ...AFA4000 2 Airflow Monitor p 87 Figure 61 Adjusting the personnel sensor beam angle away from the fume hood ...
Страница 90: ...AFA4000 2 Airflow Monitor p 90 6 10 Auto Sash System Control Box general wiring diagram ...
Страница 127: ...AFA4000 2 Airflow Monitor p 127 ...
Страница 140: ...AFA4000 2 Airflow Monitor p 140 Figure 69 Typical connection diagram ...
Страница 144: ...AFA4000 2 Airflow Monitor p 144 Figure 70 Connection diagram with RS232 485 converter ...