Chapter 9
Removing and Replacing the Servers
9-3
FIGURE 9-1
Power Supply Units and Power Sources
Caution –
Do
not
attempt to remove the server from a chassis without first
performing the next step, or you might damage major system components.
3. Unseat all rear transition modules from the server that you are going to remove.
You do not need to completely remove the rear transition modules from the chassis;
you only need to pull them out an inch or two so that they are disengaged from the
rear of the server.
4. Determine if you need to unplug the cables connected to the server and remove
all the components from the server:
■
If you are removing a
faulty
Netra CT 810 server or Netra CT 410 server, you must
unplug all the cables and remove all the components from the faulty server so
that you can reinstall them in the replacement server. Continue with
Step 5
.
Chassis
Power supply unit
Power supply unit
Power supply unit
Netra CT 810 server
Netra CT 410 server
Power supply unit
Netra CT 410 server
DC power
source A
DC power
source B
DC power
source A
DC power
source B
Содержание Netra CT 410
Страница 16: ...xvi Netra CT Server Service Manual February 2007...
Страница 20: ...xx Netra CT Server Service Manual February 2007...
Страница 28: ......
Страница 44: ...2 10 Netra CT Server Service Manual February 2007...
Страница 48: ...3 4 Netra CT Server Service Manual February 2007...
Страница 49: ...PART 2 Troubleshooting the System Troubleshooting the System Chapter 4...
Страница 50: ......
Страница 88: ......
Страница 98: ...5 10 Netra CT Server Service Manual February 2007...
Страница 138: ...6 40 Netra CT Server Service Manual February 2007...
Страница 154: ...7 16 Netra CT Server Service Manual February 2007...
Страница 176: ...8 22 Netra CT Server Service Manual February 2007...
Страница 178: ......
Страница 198: ...10 10 Netra CT Server Service Manual February 2007...
Страница 199: ...PART 5 Illustrated Parts List Illustrated Parts List Chapter 11...
Страница 200: ......
Страница 203: ...Chapter 11 Illustrated Parts List 11 3 FIGURE 11 1 Illustrated Parts of Chassis and Components 4 1 2 3...
Страница 208: ...11 8 Netra CT Server Service Manual February 2007...
Страница 210: ......
Страница 265: ...Appendix A Connector Pinouts A 55...
Страница 266: ...A 56 Netra CT Server Service Manual February 2007...
Страница 288: ...D 4 Netra CT Server Service Manual February 2007...
Страница 296: ...Index 4 Netra CT Server Service Manual February 2007 W web sites third party xxvi...