Command Reference
R&S
®
ZNB/ZNBT
1119
User Manual 1173.9163.02 ─ 38
SOURce<Ch>:POWer<PhyPt>:CORRection:NREadings
<NoCalSweeps>
Sets a limit for the number of calibration sweeps in the source power calibration. The
command is valid for all channels, ports and external generators. Equivalent command:
SOURce<Ch>:POWer<PhyPt>:CORRection:COLLect:AVERage[:COUNt]
.
Suffix:
<Ch>
.
Calibrated channel number. This parameter is ignored; the limit
applies to all sources.
<PhyPt>
Calibrated port number. This parameter is ignored; the limit
applies to all sources.
Parameters:
<NoCalSweeps>
Number of readings
Range:
1 to 100
*RST:
2
Example:
See
SOURce<Ch>:POWer<PhyPt>:CORRection[:ACQuire]
Manual operation:
See
"Flatness Cal – Max Iterations"
SOURce<Ch>:POWer<PhyPt>:CORRection:OSOurces[:STATe]
<Boolean>
Switches off all other sources during the calibration sweep for channel
<Ch>
.
Suffix:
<Ch>
.
Calibrated channel number
<PhyPt>
Calibrated port number. This parameter is ignored; the setting is
valid for all sources.
Parameters:
<Boolean>
ON - other sources not necessarily switched off.
OFF - other sources switched off during the calibration sweep.
*RST:
ON
Example:
See
SOURce<Ch>:POWer<PhyPt>:CORRection[:ACQuire]
Manual operation:
See
SOURce<Ch>:POWer<PhyPt>:CORRection:PPOWer
<RecCalPower>
Defines the source power which the R&S
ZNB/ZNBT uses to perform the first calibra-
tion sweep of the source power calibration ("Reference Receiver Cal Power"). The
power value is ignored if the R&S
ZNB/ZNBT is set to use the port power result
SOURce<Ch>:POWer<PhyPt>:CORRection:PSELect
CPOW
).
Suffix:
<Ch>
.
Calibrated channel number. This parameter is ignored; the
parameter is valid for all channels.
<PhyPt>
Calibrated port number. This parameter is ignored; the parame-
ter is valid for all sources.
SCPI Command Reference