![Mitsubishi Electric QJ71GF11-T2 Скачать руководство пользователя страница 96](http://html.mh-extra.com/html/mitsubishi-electric/qj71gf11-t2/qj71gf11-t2_user-manual_1811847096.webp)
94
Supplementary Setting
(2) Loopback Function Setting
Select whether to use the loopback function. (
Section 8.7) To configure a network in ring topology, select the
checkbox.
When "Ring" is selected in [Change Transmission Path Method]
under [CC IE Field Configuration], the checkbox will be checked.
When "Line/Star" is selected, the checkbox will be unchecked.
(
(3) Block Data Assurance per Station
Select whether to assure data integrity on a station basis in link
refresh between the CPU module and the master/local module.
(
(4) Operation Setting for Returning
When using the submaster function, select the operation of the
master station after it returns from the disconnected status. This
parameter can be set only when "Sub-Master Station" has been
selected in "Station Type".
• Loopback Function Setting:
Selected (Use)/not selected
(Default: Not selected)
• Block Data Assurance per
Station:
Selected (Assure Block Data)/
not selected
(Default: Selected (Assure
Block Data))
• Operation Setting for
Returning:
Return as Master Station,
Return as Sub-Master Station
(Default: Return as Master
Station)
Item
Description
Setting range
Содержание QJ71GF11-T2