37
CHAPTER 3 SPECIFICATIONS
3
3.
3
F
unc
tion L
is
t
(2) Transient transmission
:Available, ×: Not available
(3) RAS functions
:Available, ×: Not available
Function
Description
Availability
Reference
Master
station,
submaster
station
Local
station
Communications within the same
network
Transient transmission is performed to other
stations using dedicated instructions and GX
Works2.
Communications with different
networks
By presetting the routing parameters
(communication route) using GX Works2,
transient transmission can be performed to
stations on different networks through GX
Works2.
Seamless communications are available with
the following networks.
• Ethernet
• CC-Link IE Controller Network
• MELSECNET/H
• MELSECNET/10
• CC-Link (when using GX Works2)
Page 119, Section 7.8
Page 145, Section
8.2.2
Function
Description
Availability
Reference
Master
station,
submaster
station
Local
station
Slave station disconnection
Only the slave station where an error occurs is
disconnected, and data link continues with the
stations that are operating normally.
In a line topology, all stations connected after
the faulty station are disconnected.
×
Automatic return
When the station disconnected from the network
due to a data link failure recovers, it
automatically returns to the network and restarts
data link.
Module error collection function
An error that has occurred in a master/local
module can be stored in the CPU module as
error history.
The history data can be stored on a memory
with backup power feature, enabling retention of
the data at reset of the CPU module or power-off
of the system.
Содержание QJ71GF11-T2