APPENDICES
A
Appendix
3
Link Spec
ial
Relay (SB
) Li
st
SB0138
PORT2 current error
frame reception status
(2)
Stores if a receive frame error line status warning level has occurred in
each station's PORT2.
OFF: A receive frame error line status warning level has not yet been
occurred in any stations.
ON: A receive frame error line status warning level has been occurred
in one or more stations.
If a receive frame error line status warning level has been occurred, the
status of each station can be checked by PORT2 current error frame
reception status (each station) (2) (SW0138 to SW013F).
Depending on the timing of the link refresh, the update of PORT2 current
error frame reception status (each station) (2) (SW0138 to SW013F)
may be offset by one sequence scan.
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
SB0139
PORT2 current error
frame reception status
(station No.0) (2)
Stores if a receive frame error line status warning level has occurred in
the PORT2 of station number 0.
OFF: A receive frame error line status warning level has not yet been
occurred.
ON: A receive frame error line status warning level has been occurred.
(Condition)
• This is enabled when the submaster function is used.
SB013F
PORT2 current error
frame reception status
(station No.0) (1)
Stores if a receive frame error line status caution level has occurred in
the PORT2 of station number 0.
OFF: A receive frame error line status caution level has not yet been
occurred.
ON: A receive frame error line status caution level has been occurred.
(Condition)
• This is enabled when the submaster function is used.
SB0140
PORT1 error frame
reception detection
status (1)
Stores if a receive frame error line status caution level has occurred in
each station's PORT1 from power-on until the present.
OFF: A receive frame error line status caution level has not yet been
occurred in any stations.
ON: A receive frame error line status caution level has been occurred
in one or more stations.
If a receive frame error line status caution level has been occurred, the
status of each station can be checked by PORT1 error frame reception
detection status (1) (SW0140 to SW0147).
Depending on the timing of the link refresh, the update of PORT1 error
frame reception detection status (1) (SW0140 to SW0147) may be offset
by one sequence scan.
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
Number
Name
Description
Availability
Master
station
(submaster
station)
Local
station