CHAPTER 7 PARAMETER SETTING
7
7.
2
N
et
w
ork
S
et
tings
Network No.
Enter the network number of the master/local module.
When mounting modules with the same network number on the same
base unit, observe the following.
• One master station and one submaster station can be set.
• Multiple local stations can be set.
1 to 239 (Default: Blank)
Total Stations
Set the total number of stations in a network (excluding the master
station).
• If any reserved station is required, include the number of reserved
stations.
• If the submaster station is connected, include the number of
submaster stations.
The number can be set when "CC IE Field (Master Station)" or "CC IE
Field (Sub-Master Station)" is selected in "Network Type".
When the checkbox next to "Set the network configuration setting in
the CC IE Field configuration window" is selected, the setting value in
the CC IE Field configuration setting window is displayed.
• Master station:
1 to 120 (Default: Blank)
• Submaster station:
"0" or same as the master station
setting (Default: 0)
Station No.
Enter the station number of the master/local module. Set a station
number different from those used in the same network.
The station number of the master station is fixed to "0".
To set the station number of a local station in this setting, select
"Specify Station No. by Parameter". (If "Specify Station No. by
Program" is selected, the station number cannot be set in this setting.)
When "CC IE Field (Sub-Master Station)" is selected for "Network
Type" and the following setting is configured, the setting value in the
CC IE Field configuration window is displayed.
• Check the checkbox next to "Set the network configuration setting
in the CC IE Field configuration window" and select "Operate with
Parameter of Host Station".
• Master station: Fixed to "0"
• Local station, submaster station:
1 to 120 (Default: Blank)
Item
Description
Setting range