500
SW0062
Current link scan time
Stores the current value of the link scan time during cyclic transmission.
The stored value contains a maximum error of 1 ms. (Unit: ms)
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
SW0063
Constant link scan set
value
Stores the setting value of the contact link scan that is set in the
supplementary setting.
0: No setting
1 to 200: Setting value of contact link scan time (Unit: ms)
(Condition)
• This is enabled when Data link status (own station) (SB0049) is off.
SW0064
Connection status
(own station)
Stores the connection status of own station.
00
H
: Normal (communication in progress on PORT1 and PORT2)
01
H
: Normal (communication in progress on PORT1, cable
disconnected
on PORT2)
04
H
: Normal (loopback communication in progress on PORT1, cable
disconnected on PORT2)
10
H
: Normal (cable disconnected on PORT1, communication in
progress on PORT2)
11
H
: Disconnecting (cable disconnected on PORT1 and PORT2)
12
H
: Disconnecting (cable disconnected on PORT1, establishing line on
PORT2)
21
H
: Disconnecting (establishing line on PORT1, cable disconnected on
PORT2)
22
H
: Disconnecting (establishing line on PORT1 and PORT2)
40
H
: Normal (cable disconnected on PORT1, loopback communication
in progress on PORT2)
SW0066
Actual link scan time
(lower 1 word)
Stores the link scan time during cyclic transmission. (Unit: µs)
SW0067
Actual link scan time
(upper 1 word)
SW0068
PORT1 receive error
occurrence rate (own
station) (max.)
Stores the occurrence rate (maximum value) of received error frames at
the own station's PORT1. (Unit: %)
When Clear communication error count (SB0006) is turned on, the
stored occurrence rate is cleared.
SW0069
PORT1 receive error
occurrence rate (own
station) (present)
Stores the occurrence rate (current value) of received error frames at the
own station's PORT1. (Unit: %)
When Clear communication error count (SB0006) is turned on, the
stored occurrence rate is cleared.
SW006A
PORT2 receive error
occurrence rate (own
station) (max.)
Stores the occurrence rate (maximum value) of received error frames at
the own station's PORT2. (Unit: %)
When Clear communication error count (SB0006) is turned on, the
stored occurrence rate is cleared.
Number
Name
Description
Availability
Master
station
(submaster
station)
Local
station
Содержание QJ71GF11-T2
Страница 1: ...MELSEC Q CC Link IE Field Network Master Local Module User s Manual QJ71GF11 T2 ...
Страница 2: ......
Страница 558: ...556 Appendix 12External Dimension Diagram 27 4 23 115 98 4 Unit mm ...
Страница 559: ...557 APPENDICES A Appendix 12 External Dimension Diagram Memo ...
Страница 567: ......