384
• When failed
(3) Checking error details
If the dedicated instruction fails, error details can be checked by either of the following methods:
(a) In GX Works2
Error details can be checked using the CC-Link IE Field Network diagnostics. (
(b) Using devices
Completion status indication device ((D1)+1) turns on, and an error code is stored in Completion status
((S1)+1) of the control data.
According to the error code, check the error details and take a corrective action.
(
1 scan
UINI
Sequence scan
Start contact
Own station CPU
Local station
Completion device
(Device specified in (D1))
Completion status
indication device
(Device of (D1) + 1)
Error code
Completion status
(Device of (S1) + 1)
END
0
END
0
Station number setting error
END
0
END
0
END
0
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON