CHAPTER 12 TROUBLESHOOTING
12
12.
5
E
rror
Code
List
D646
H
Parameter error (operation setting)
• Write the network parameters to the CPU module again.
• To start the master/local module as a master station, set 0 or 2 for Switch
4 in the intelligent function module switch setting of the module.
• To start the master/local module as a local station, set 0 for Switch 4 in the
intelligent function module switch setting of the module.
• To start the master/local module as a submaster station, set 0 or 4 for
Switch 4 in the intelligent function module switch setting of the module.
• If this error persists, please consult your local Mitsubishi representative.
D701
H
Temporary reserved station cancel/
temporary error invalid station setting
not set
Set the target station(s) in Reserved station function disable/temporary error
invalid station setting (SW0010 to SW0017), and retry the operation.
D706
H
Request error of temporary error
invalid station setting/cancel or
reserved station cancel/restoration
(when the own station is a local
station)
Temporary error invalid station setting/cancel or reserved station setting
cancel/restoration cannot be executed from a local station or submaster
operating station. Retry the operation from the master operating station.
D70B
H
Request error of temporary error
invalid station setting/cancel or
reserved station cancel/restoration
(when different settings are
simultaneously performed)
• Temporary error invalid station setting/cancel using SB0010 and SB0011
or reserved station cancel/restoration using SB0012 and SB0013 cannot
be simultaneously executed.
• Retry the operation so that only one bit in SB0010 to SB0013 may turn on
after all bits in them are turned off.
D720
H
Data link start/stop instruction out of
range
Check the setting, and stop or start data link.
D721
H
Data link start/stop retry error (another
station)
Retry the operation after the stop or restart of data link is completed.
D722
H
Data link start/stop retry error (own
station)
Retry the operation after the stop or restart of data link is completed.
D723
H
Data link start/stop retry error (entire
system)
Retry the operation after the stop or restart of data link is completed.
D724
H
Data link start/stop station error
Check the setting, and stop or start data link.
D725
H
Station type error (station that starts/
stops data link throughout the entire
system)
A local station and a submaster operating station cannot start or stop data
link of all or multiple stations. Perform these operations from the master
operating station.
D726
H
Transient data request command error Correct the request command at the request station, and retry the operation.
D727
H
Data link start/stop command-
instructing stations different
• Data link start was instructed from a station different from the one that had
instructed the data link stop. Instruct data link start and data link stop from
the same station.
• The method of the data link start differs from that of the data link stop.
Instruct the data link start using the same method as the data link stop (ex.
Data link is stopped using the CC-Link IE Field Network diagnostics, and
the data link is started using a program).
• Data link start failed. Forcibly restart the data link.
D728
H
Data link start/stop command-
instructing stations different
Data link start was instructed during execution of data link. Instruct data link
stop then data link start.
D729
H
UINI instruction not executed
Set the station number using the UINI instruction.
D731
H
Forced master switch error
Perform the forced master switch to the submaster station operating as a
master operating station.
D740
H
Transient transmission failed
• If a slave station is disconnected from the network, identify the cause of
the disconnection and take action.
• When data link is stopped in the slave station, identify the cause of the
data link stop and take action.
• Retry the operation after a slave station is replaced and new one is added.
Error code
Error
Action