452
D613
H
Parameter error (device range
assignment error (RWr))
• Write the network parameters to the CPU module again.
• Correct the value in the size of the link device in the slave station(s)
(setting data), and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D614
H
Parameter error (device range
assignment error (RWr))
• Write the network parameters to the CPU module again.
• Correct the value in the size of the link device in the slave station(s)
(setting data), and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D615
H
Parameter error (device range
assignment error (RY))
• Write the network parameters to the CPU module again.
• Correct the value in the size of the link device in the slave station(s)
(setting data), and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D616
H
Parameter error (device range
assignment error (RY))
• Write the network parameters to the CPU module again.
• Correct the value in the size of the link device in the slave station(s)
(setting data), and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D617
H
Parameter error (device range
assignment error (RX))
• Write the network parameters to the CPU module again.
• Correct the value in the size of the link device in the slave station(s)
(setting data), and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D618
H
Parameter error (device range
assignment error (RX))
• Write the network parameters to the CPU module again.
• Correct the value in the size of the link device in the slave station(s)
(setting data), and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D619
H
to D61A
H
Parameter error
• Write the network parameters to the CPU module again.
• If this error persists, please consult your local Mitsubishi representative.
D61B
H
Parameter error (device already in use
(RWw))
• Write the network parameters to the CPU module again.
• Correct the value in the offset or the size of the link device in the slave
station(s) (setting data), and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D61C
H
Parameter error (device already in use
(RWr))
D61D
H
Parameter error (device already in use
(RY))
D61E
H
Parameter error (device already in use
(RX))
D61F
H
CCPASET execution error
Delete the network parameter settings in the programming tool, execute
"Write to PLC", and execute the CCPASET instruction again.
D620
H
Incorrect transient data
• Check the transient data at the request source, and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D621
H
Parameter error
• Write the network parameters to the CPU module again.
• If this error persists, please consult your local Mitsubishi representative.
D622
H
Parameter error (total number of slave
stations error)
• Write the network parameters to the CPU module again.
• Correct the total number of slave stations, and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D623
H
Parameter error (link scan mode error)
• Write the network parameters to the CPU module again.
• Correct the link scan mode, and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D624
H
Parameter error (constant link scan
time setting error)
• Write the network parameters to the CPU module again.
• Correct the value in the total number of slave stations (setting data), and
retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D625
H
Parameter error (block data assurance
per station setting error)
• Write the network parameters to the CPU module again.
• Correct the value in the total number of slave stations (setting data), and
retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
Error code
Error
Action