368
(c) Reserved station specification data (master station (needs to be set) and submaster
station only)
When Reserved station specification data (b1) in Setting flag ((S1)+1) is set to valid, store the slave station
number to be reserved.
*1
When a station is set as both error invalid station and reserved station, the reserved station setting takes priority.
(d) Error invalid station setting data (master station (needs to be set) and submaster
station only)
When Error invalid station setting data (b2) in Setting flag ((S1)+1) is set to valid, store the slave station number
for which error invalid station setting is to be configured.
*1
When a station is set as both error invalid station and reserved station, the reserved station setting takes priority.
Device
Item
Setting data
Set by
(S3)+0 to
(S3)+7
Reserved station
specification
*1
Specify the reserved stations.
0: Not specified (default)
1: Specified
Do not set a submaster station number as a reserved station number. Doing so will cause an
error.
User
Device
Item
Setting data
Set by
(S4)+0 to
(S4)+7
Error invalid
station setting
*1
Specify error invalid stations.
0: Not specified (default)
1: Specified
Do not set a submaster station number as an error invalid station number. Doing so will cause
an error.
User
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
120 119 118 117 116 115 114 113
Each number in the table represents station No.
(S3)+0
(S3)+1
(S3)+2
(S3)+3
(S3)+4
(S3)+5
(S3)+6
(S3)+7
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
120 119 118 117 116 115 114 113
Each number in the table represents station No.
(S4)+0
(S4)+1
(S4)+2
(S4)+3
(S4)+4
(S4)+5
(S4)+6
(S4)+7