476
SB0045
Station setting (own
station) (2)
This stores if the own station is a local station or not.
OFF: Not local station
ON: Local station
(Condition)
• This is enabled when Station setting (own station) (1) (SB0044) is off.
SB0046
Station number setting
status of the own
station
The setting status of the station number is stored.
OFF: Station number set
ON: Station number not set
When the station number is set using the parameter of GX Works2, this
link special relay is always off.
×
SB0047
Baton pass status (own
station)
Stores the baton pass status for the own station (transient transmission
possible).
OFF: Normal
ON: Error
If an error occurs, the cause of the error can be checked by the Baton
pass status (own station) (SW0047) and Cause of baton pass
interruption (SW0048).
Depending on the timing of the link refresh, the update of Baton pass
status (own station) (SW0047) and Cause of baton pass interruption
(SW0048) may be offset by one sequence scan.
SB0049
Data link status (own
station)
Stores the own station's data link status.
OFF: Normal
ON: Error
If an error occurs, the cause of the error can be checked by Cause of
data link stop (SW0049).
Depending on the timing of the link refresh, the update of Cause of data
link stop (SW0049) may be offset by one sequence scan.
(Conditions)
• This is enabled when Baton pass status (own station) (SB0047) is
OFF.
SB004A
Own station's CPU
status (1)
Stores the continuation error status of the own station's CPU module.
OFF: Normal
ON: Continuation error
SB004B
Own station's CPU
status (2)
Stores the stop error status of the own station's CPU module.
OFF: Normal
ON: Stop error
SB004C
CPU RUN status (own
station)
Stores the RUN status of the own station's CPU module.
OFF: RUN, STEP-RUN
ON: STOP, PAUSE, or CPU module stopped due to error
SB004D
Received parameter
error
Stores the status of the received parameter. (own parameter status
during master station)
OFF: Parameter normal
ON: Parameter error
Number
Name
Description
Availability
Master
station
(submaster
station)
Local
station