490
SB0141
PORT1 error frame
detection (master
station)
Stores if an error frame was received from power-on until the present at
the master station's PORT1.
OFF: An error frame has not yet been received
ON: An error frame has been received at least once
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
SB0148
PORT1 error frame
reception detection
status (2)
Stores if a receive frame error line status warning level has occurred in
each station's PORT1 from power-on until the present.
OFF: A receive frame error line status warning level has not yet been
occurred in any stations.
ON: A receive frame error line status warning level has been occurred
in one or more stations.
If a receive frame error line status warning level has been occurred, the
status of each station can be checked by PORT1 error frame reception
detection status (2) (SW0148 to SW014F).
Depending on the timing of the link refresh, the update of PORT1 error
frame reception detection status (2) (SW0148 to SW014F) may be offset
by one sequence scan.
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
SB0149
PORT1 error frame
reception detection
status (station No.0) (2)
Stores if a receive frame error line status warning level has occurred in
the PORT1 of station number 0 from power-on until the present.
OFF: A receive frame error line status warning level has not yet been
occurred.
ON: A receive frame error line status warning level has been occurred
at least once.
(Condition)
• This is enabled when the submaster function is used.
SB014F
PORT1 error frame
reception detection
status (station No.0) (1)
Stores if a receive frame error line status caution level has occurred in
the PORT1 of station number 0 from power-on until the present.
OFF: A receive frame error line status caution level has not yet been
occurred.
ON: A receive frame error line status caution level has been occurred
at least once.
(Condition)
• This is enabled when the submaster function is used.
Number
Name
Description
Availability
Master
station
(submaster
station)
Local
station
Содержание QJ71GF11-T2
Страница 1: ...MELSEC Q CC Link IE Field Network Master Local Module User s Manual QJ71GF11 T2 ...
Страница 2: ......
Страница 558: ...556 Appendix 12External Dimension Diagram 27 4 23 115 98 4 Unit mm ...
Страница 559: ...557 APPENDICES A Appendix 12 External Dimension Diagram Memo ...
Страница 567: ......