![Mitsubishi Electric QJ71GF11-T2 Скачать руководство пользователя страница 301](http://html.mh-extra.com/html/mitsubishi-electric/qj71gf11-t2/qj71gf11-t2_user-manual_1811847301.webp)
299
CHAPTER 10 DEDICATED INSTRUCTIONS
10
10.
9
J
P
/G
P
.R
ECV
(Re
ceiving D
a
ta
fr
om
t
he
Progr
amm
abl
e
Cont
roller on
Anot
her
St
at
ion)
(4) Program example
The following program is for reading the data sent from station No.0 by the SEND instruction, into channel 2 of
station No.2 (own station) to D770 to D773, when SB0031 is turned on.
For details on the SEND instruction, refer to the following.
(a) System configuration
Same as the SEND instruction program example.
(b) Devices used in the program
• Link special relay (SB)
Remark
For details on the link special relay (SB), refer to the following.
• Devices used by users
Device
Description
Device
Description
SB0031
RECV execution request flag (2)
Device
Description
Device
Description
M165
Completion device
D370 to
D387
Control data
M166
Completion status indication device
D770 to
D773
Receive data storage device