380
10.18
Z/ZP.UINI (Own Station (Local Station) Number Setting)
This instruction sets a station number for a local station (own station).
When there are local stations with the same program and network parameters (excluding the station numbers), setting
the station numbers using a program allows project data items other than the station number to be the same, leading to
reduced development work hours.
Set network parameters other than a station number parameter using GX Works2 or the CCPASET instruction.
10.18.1
Procedure for setting a station number using the UINI
instruction
(1) Procedure
(a) Setting a station number using the UINI instruction and other items using GX
Works2
1.
Set parameters other than a station number parameter using network parameters. (
2.
Set "Specify Station No. by Program" in the network parameter window.
Project window
[Parameter]
[Network Parameter]
[Ethernet/CC IE/MELSECNET]
3.
Create a UINI instruction program. (
4.
Write the UINI instruction program to the CPU module through GX Works2.
[Online]
[Write to PLC]
5.
Execute the UINI instruction in the CPU module on the local station (own station).
(b) Setting a station number using the UINI instruction and other items using the
CCPASET instruction
1.
Open the "I/O Assignment" tab of GX Works2.
Project window
[Parameter]
[PLC Parameter]
"I/O Assignment" tab