223
CHAPTER 9 CC-LINK IE FIELD NETWORK DIAGNOSTICS
9
9.
5
N
e
tw
ork
E
vent
Hist
o
ry
9.5
Network Event History
The history of events occurred in the own station and in the network can be displayed. When the master station is the
target module, event history of the entire network can be displayed. The history data are useful for troubleshooting at
the start of the network system.
(1) Displaying event history
●
The number of displayed events
Up to 1000 events can be displayed. When the maximum is reached, the events will be erased in sequence starting from
the oldest one and the latest events will be displayed.
●
Incorrect display of error occurrence time and date
For the master/local module with a serial number (first five digits) of "17051" or earlier, if an error occurs during initial
processing of the CPU module, "0000/00/00 00:00:00" will be displayed.
1.
Connect GX Works2 to the CPU module.
2.
Start the CC-Link IE Field Network diagnostics from
the menu.
[Diagnostics]
[CC IE Field Diagnostics]
3.
Click the
button in the "CC IE
Field Diagnostics" window.
Or right-click a module icon in "Network Status",
and click [Network Event History].
The "Network Event History" window opens.
4.
Click the
button to select the
events to be collected.
5.
Select events to be collected and click the
button.
Events that can be collected depend on the station type
(master station or local station).
6.
Click each title to sort the events.