CHAPTER 8 FUNCTIONS
8
8.
1
C
ycl
ic
Tra
n
smi
ssi
on
8.
1.
7
Input
and out
put
st
at
us s
et
tings
in
cas
e of
f
ail
ur
e
(1) Setting method
(a) Input status of data link faulty station
Set this item in the "Network Operation Settings" window. (
(b) Cyclic data output when a stop error occurs in the CPU module
Select "PLC Parameter" and set it in "Intelligent Function Module Detailed Setting".
[Project Window]
[Parameter]
[PLC Parameter]
"I/O Assignment" tab
button
"Error Time Output Mode"
(2) Precautions
(a) When data link is stopped by users
When cyclic transmission is stopped using one of the following methods, the input status of the faulty station is
held.
• CC-Link IE Field Network diagnostics (
• Link special relay (SB), link special register (SW) (
(b) Setting on a station with a data link error
When the following settings are set to "Hold" on the station where a data link error has occurred, the input
status of the own station upon error is held, regardless of setting.
• "Network Operating Settings"
"Output Setting During CPU STOP" (
• "PLC Parameter"
"Intelligent Function Module Detailed Setting"
"Error Time Output Mode"
(