503
APPENDICES
A
Appendix
4
Link Spec
ial
Regist
er
(S
W
) List
SW00A0
to
SW00A7
Baton pass status
(each station)
Stores the baton pass status for each station.
0: Baton pass normal station
1: Baton pass faulty station
• If multiple stations change from faulty to normal, because they are
reconnected to the network one by one per link scan, the time until the
status changes to "0: Baton pass normal station" may vary by several
seconds.
• If cables are connected/disconnected or the module is reset in line and
ring topologies, the token may be lost or a reconstruction may occur,
causing the baton pass status to detect an error in the first link scan.
(Conditions)
• This is enabled when Baton pass status (own station) (SB0047) is off.
• Reserved stations and stations higher than the maximum station No.
are ignored.
Number
Name
Description
Availability
Master
station
(submaster
station)
Local
station
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
120 119 118 117 116 115 114 113
Each number in the table represents a station No.
is fixed to 0.
SW00A1
SW00A2
SW00A3
SW00A4
SW00A5
SW00A6
SW00A7
SW00A0
Содержание QJ71GF11-T2
Страница 1: ...MELSEC Q CC Link IE Field Network Master Local Module User s Manual QJ71GF11 T2 ...
Страница 2: ......
Страница 558: ...556 Appendix 12External Dimension Diagram 27 4 23 115 98 4 Unit mm ...
Страница 559: ...557 APPENDICES A Appendix 12 External Dimension Diagram Memo ...
Страница 567: ......