154
●
When an Ethernet device is connected to a module, such as an Ethernet adapter module, that does not support the
routing parameters
Set the routing parameters so that communications are transmitted through the master station.
Communications from a module that does not have the routing parameters are automatically transmitted through the
master station. The communication routes must be the same for data sending and receiving; therefore, configure the
setting so that communications are transmitted through the master station.
Proper setting
Improper setting
*1
An IP communication test related error (error code: 4A28
H
) occurs in the IP communication test.
Ex.
A
B
C
Ethernet device
(request source device)
Ethernet device
(request destination device)
Local station
Master station
Network No.1
Network No.2
Communication routes set using the routing
parameters
Communication route automatically set
(from a module that does not have the routing
parameters to the master station)
Network No.3
Target
Network No.
Relay
Network No.
Relay
Station No.
The setting is not required
because the module does not
have the routing parameters.
Set this column to pass communications
through the master station.
Target
Network No.
Relay
Network No.
Relay
Station No.
3
0
2
1
1
2
3
2
2
Station
No.2
Station
No.1
Setting for
A
Setting for
B
Setting for
C
Station
No.0
Ex.
A
B
C
Ethernet device
(request source device)
Ethernet device
(request destination device)
Local station
Master station
Network No.1
Network No.2
Communication routes set using the routing
parameters
Communication route automatically set
(from a module that does not have the routing
parameters to the master station)
Network No.3
Target
Network No.
Relay
Network No.
Relay
Station No.
The setting is not required
because the module does not
have the routing parameters.
Because the communication route for data sending is different
from that for data receiving, an error occurs.*
1
Target
Network No.
Relay
Network No.
Relay
Station No.
3
2
2
1
1
2
Station
No.2
Station
No.1
Setting for
A
Setting for
B
Setting for
C
Station
No.0