277
CHAPTER 10 DEDICATED INSTRUCTIONS
10
10.
7
J
P
/G
P
.S
W
R
IT
E
(W
rit
ing Dat
a
t
o
the
Progr
amm
able Cont
roller on
A
n
ot
her
St
at
ion)
(1) Setting data
(a) Control data
The control data of the SWRITE instruction control data is the same as that of the WRITE instruction
(
(b) Start device of the own station where data to be written is stored
The start device of the own station where data to be written by the SWRITE instruction is stored is the same as
that of the WRITE instruction. (
(c) Start device of the target station where data is to be written
The start device of the target station is the same as that of the WRITE instruction. (
Setting data
Description
Set by
Data type
Jn
Own station's network No. (1 to 239, 254)
254: Network specified in Valid Module During Other Station Access
User
16-bit binary
Un
Start I/O number of the master/local module of the own station
(00 to FE
H
: Upper two digits of the I/O number expressed in three
digits)
(S1)
Start device of the own station where control data is stored
Device name
(S2)
Start device of the own station where data to be written is stored
(D1)
Start device of the target station where data is to be written
(A continuous area with the write data length is required.)
System
(D2)
The device of the own station that turns on for one scan upon
completion of the instruction.
If the instruction fails, (D2)+1 also turns on.
Bit
(D3)
Device of the target station, which is turned on for 1 scan upon
completion of the instruction.
(Data writing from another station can be confirmed.)