6.2
Tests Before Wiring
This section describes module tests that should be performed before network wiring.
6.2.1
Hardware test
Hardware test checks the hardware inside the master/local modules.
(1) Procedure
1.
Mount the master/local module on the base unit and
connect GX Works2 to the CPU module.
An Ethernet cable is not connected to the master/local
modules.
2.
Set network parameters as shown in the figure to
left.
Project window
[Parameter]
[Network
Parameter]
[Ethernet/CC IE/MELSECNET]
3.
Write the network parameters set to the CPU
module.
[Online]
[Write to PLC]
4.
Reset the CPU module or power off and then on the
system.
5.
Hardware test begins.
The MODE LED of master/local modules flashes, and
each of the ×1 LED repeatedly turns on and off (1
2
4
8
1 • • •).
Select "H/W Test".
Select "CC IE Field (Master Station)",
"CC IE Field (Local Station)",
or CC IE Field (Sub-Master Station).
or power OFF ON
RESET
RUN
SD
ERR.
MST
D LINK
RD
L ERR.
1
2
4
8
MODE
X100 10
1
S
T
N
O
.
.
1
2
4
8
1
: On
: Flashing