424
(14)Setting/Canceling a temporary error invalid station
Setting/Canceling a temporary error invalid station is executed using the CC-Link IE Field Network diagnostics as
well as link special relays (SBs) and link special registers (SWs). (
(a) Setting a temporary error invalid station
1.
Specify the station number to set a temporary error invalid station in Reserved station function
disable/temporary error invalid station setting (SW0010 to SW0017),
2.
Turn on Temporary error invalid request (SB0010).
3.
Temporary error invalid request accept status (SB0058) is turned on.
4.
When a temporary error invalid station is set, Temporary error invalid setting completion status
(SB0059) turns on.
5.
Temporary error invalid station setting status (SB00E0) turns on, and the station number of the
temporary error invalid station is stored in Temporary error invalid station setting status (SW00E0
to SW00E7).
6.
When the temporary error invalid station is set with error, an error code will be stored in
Temporary error invalid station setting result (SW0054).
7.
Turn off Temporary error invalid request (SB0010).
(b) Canceling a temporary error invalid station
1.
Specify the station number to cancel a temporary error invalid station in Reserved station function
disable/temporary error invalid station setting (SW0010 to SW0017).
2.
Turn on Temporary error invalid setting cancel request (SB0011).
3.
Temporary error invalid setting cancel request accept status (SB005A) is turned on.
4.
When the cancellation is completed, Temporary error invalid setting cancel completion status
(SB005B) turns on.
5.
Use Temporary error invalid station setting status (SW00E0 to SW00E7) to check if the temporary
error invalid station setting is cancelled. When the network no longer has a temporary error invalid
station, Temporary error invalid station setting status (SB00E0) turns off.
6.
When the temporary error invalid station is cancelled with error, an error code will be stored in
Temporary error invalid station setting cancel result (SW0055).
7.
Turn off Temporary error invalid setting cancel request (SB0011).
Number
Description
Number
Description
SB0010
Temporary error invalid request
SW0010 to
SW0017
Reserved station function disable/temporary error
invalid station setting
SB0058
Temporary error invalid request accept status
SW0054
Temporary error invalid station setting result
SB0059
Temporary error invalid setting completion status
SB00E0
Temporary error invalid station setting status
SW00E0 to
SW00E7
Temporary error invalid station setting status
Number
Description
Number
Description
SB0011
Temporary error invalid setting cancel request
SW0010 to
SW0017
Reserved station function disable/temporary error
invalid station setting
SB005A
Temporary error invalid setting cancel request accept
status
SW0055
Temporary error invalid station setting cancel result
SB005B
Temporary error invalid setting cancel completion
status
SB00E0
Temporary error invalid station setting status
SW00E0 to
SW00E7
Temporary error invalid station setting status
Содержание QJ71GF11-T2
Страница 1: ...MELSEC Q CC Link IE Field Network Master Local Module User s Manual QJ71GF11 T2 ...
Страница 2: ......
Страница 558: ...556 Appendix 12External Dimension Diagram 27 4 23 115 98 4 Unit mm ...
Страница 559: ...557 APPENDICES A Appendix 12 External Dimension Diagram Memo ...
Страница 567: ......