CHAPTER 12 TROUBLESHOOTING
12
12.
5
E
rror
Code
List
D626
H
Parameter error (loopback setting
error)
• Write the network parameters to the CPU module again.
• Correct the value in the total number of slave stations (setting data), and
retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D627
H
Parameter error (slave station setting
information error)
• Write the network parameters to the CPU module again.
• Correct the value in the total number of slave stations (setting data), and
retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D628
H
Parameter error (station type error)
• Write the network parameters to the CPU module again.
• Correct the value in the total number of slave stations (setting data), and
retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D629
H
Parameter error (Station No. range
error)
• Write the network parameters to the CPU module again.
• Change the station number in the setting data to any of 1 to 120, and retry
the operation.
• If this error persists, please consult your local Mitsubishi representative.
D62A
H
Parameter error (data link faulty
station setting error)
• Write the network parameters to the CPU module again.
• Correct the output status setting for CPU STOP, and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D62B
H
Parameter error (output status setting
for a CPU STOP error)
• Write the network parameters to the CPU module again.
• Correct the output status setting for CPU STOP, and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D62C
H
Parameter error (interrupt setting
error)
• Write the network parameters to the CPU module again.
• Correct the interrupt settings and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
D62D
H
Data link start failed
Data link start failed due to any of the following causes. Remove the error
cause, and retry the operation.
• Station No. not set
• CPU module error on the own station
• More than one master station or submaster station exists.
• Station type mismatch
• Master station lost
• Own station No. out of range
• Station No. already in use (own station)
• Own station reserved
• Parameter error
• Parameter communication in progress
• Parameters not received (master station only and no slave station exists)
• Link stop command
D630
H
Execution error at the local station
(CCPASET)
Configure the network number, station type, and station number in the
switch setting.
Then execute the instruction again with the network parameter not set.
D634
H
Parameter error (incorrect number of
submaster stations)
• Write the network parameters to the CPU module again.
• Set one submaster station in the station type set for each station and retry
the operation.
• If this error persists, please consult your local Mitsubishi representative.
D635
H
Parameter error (incorrect submaster
station number)
• Write the network parameters to the CPU module again.
• Set the station number within 1 to 120 and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
Error code
Error
Action