382
10.18.2
Instruction details
The Z/ZP.UINI instructions set a station number for a local station.
*1
The double quotation marks around the first argument can be omitted.
*2
Local devices and file registers set for each program cannot be used.
(1) Setting data
(a) Control data
Setting
data
*2
Available devices
Internal device
(System, user)
File
register
R, ZR
Link direct device
J
\
Intelligent function
module device
U
\
G
Index register
Zn
Constant
Others
Bit
Word
Bit
Word
K, H
$
(S1)
(D1)
Setting data
Description
Set by
Data type
"Un"/Un
Start I/O number of the local station (own station)
(00 to FE
H
: Upper two digits of the I/O number expressed in three
digits)
User
16-bit binary
(S1)
Start device of the own station where control data is stored
Device name
(D1)
The device of the own station that turns on for one scan upon
completion of the instruction.
If the instruction fails, (D1)+1 also turns on.
System
Bit
Device
Item
Setting data
Setting range
Set by
(S1)+0
Unused
System
(S1)+1
Completion status
The status of when the instruction is ended is stored.
0: Normal
Values other than 0: Error (
System
(S1)+2
Target station
setting
Specify whether to set a station number for the own station.
0: Do not set a station number
1: Station number set
0 and 1
User
(S1)+3
Own station
number
Set a station number.
1 to 120
User
(S1)+4 to
(S1)+9
Unused
System
Z.UINI
Start contact
ZP.UINI
Start contact
Z.UINI
"Un"
ZP.UINI
"Un"
(S1)
(D1)
(S1)
(D1)
*1
*1