(b) Change Transmission Path Method
[CC IE Field Configuration]
[Change Transmission Path Method]
RWw/RWr Setting
Assign RWw/RWr points in increments of 4. (
When "Sub-Master Station" is selected in "Station Type", points can also be
assigned for the master station. (
To equally assign points or the same points, go to [Equal Assignment] or
[Identical Point Assignment] under [CC IE Field Configuration].
(
• Points:
• Device number: 0 to 1FFF
H
(Default: varies depending on the set
module)
Refresh Device
Link refresh target devices in the CPU module are displayed for each link
device of the master/local module.
Target devices are displayed when refresh parameters have been set.
(
Reserved/Error
Invalid Station
Set this item to reserve the slave station or to set the slave station as an
error invalid station. (
This item cannot be set for the submaster station.
• No Setting
The slave station is connected to the network.
• Reserved Station
The slave station is reserved for future expansion. By reserving a slave
station, link device assignment will not change even if the slave station is
added or the reservation is cancelled. Therefore, the program needs not
to be modified. Physical connection of the slave station is not required.
• Error Invalid Station
Even if a slave station is disconnected during data link, the master station
will not detect the slave station as a faulty station.
• No Setting
• Reserved Station
• Error Invalid Station
(Default: No Setting)
Alias
Enter the name of a device if required.
The name entered is displayed in "Network Status" of the CC-Link IE Field
diagnostics.
However, even if the name of the extension module connected to the
remote device station is entered, the name is not displayed in the CC-Link
IE Field diagnostics.
Up to 8 characters
(Default: Blank)
Comment
Information entered in "Comment1" on the "Property" window displayed by
right-clicking on the module in "List of stations" or "Configuration of the
devices" is displayed.
Up to 32 characters
(Default: Blank)
Station-specific
mode setting
Set the station-specific mode of the slave station. This setting is available
only when the slave station supports the station-specific mode.
The setting varies depending on the
set module.
Module List
The slave stations are listed. Drag and drop the modules from "Module List"
to the station list area or the device map area to set the information of the
slave stations into the master station.
Item
Description
Setting range
Station Type
Setting
range
Master Station, Local
Station, Intelligent
Device Station, Sub-
Master Station
4 to 1024
Remote Device Station
4 to 64
Remote I/O Station
Cannot be
set.
Содержание QJ71GF11-T2
Страница 1: ...MELSEC Q CC Link IE Field Network Master Local Module User s Manual QJ71GF11 T2 ...
Страница 2: ......
Страница 558: ...556 Appendix 12External Dimension Diagram 27 4 23 115 98 4 Unit mm ...
Страница 559: ...557 APPENDICES A Appendix 12 External Dimension Diagram Memo ...
Страница 567: ......