Parameter
Name / value range / [default setting]
Info
0x2540:005
(PAR 208/005)
Mains voltage: Overvoltage warning threshold
(Mains volt. sett.: OU warning level)
0 ... [0]* ... 800 V
•
Default setting depending on the size.
Setting of the warning threshold for monitoring DC bus overvoltage.
•
If the DC bus voltage exceeds the threshold set, the inverter outputs a
warning.
•
The warning is reset with a hysteresis of 10 V.
0x2540:006
(PAR 208/006)
Mains voltage: Overvoltage error threshold
(Mains volt. sett.: OU error level)
•
Read only: x V
•
Default setting depending on the size.
Display of the fixed error threshold for monitoring the DC bus overvolt-
age.
•
If the DC-bus voltage exceeds the threshold displayed, the "Fault"
response is triggered.
0x2540:007
(PAR 208/007)
Mains voltage: Overvoltage reset threshold
(Mains volt. sett.: OU deletion level)
•
Read only: x V
•
Default setting depending on the size.
Display of the fixed reset threshold for monitoring DC bus overvoltage.